Relevant Standard


EN 60598-1

EN 61000-3-2

IEC 60598-1

IEC61000-3-2

EN 60598-2-22

EN 61000-3-3

IEC 60598-2-22

IEC 61000-3-3

EN 61347-1

EN 62471

IEC 61347-1

IEC 62471

EN 61347-2-13

EN 62493

IEC 61347-2-13

IEC 62493

EN 61347-2-7

EN 55015

IEC 61347-2-7

IEC 55015

EN 62778

EN62031

IEC 62778

IEC62031


 

Product Parameter

Model No.:

LEK02-3NC

Battery:

Ni-Cd, 3.6V 2000mAh

LED Chips:

CREE XT-E

Luminous Flux:

150lm

Power Consumption:

3W

Input Voltage:

AC220-240V~50/60Hz

Charge time:

24Hours

Emergency duration:

3Hours

ta:

0~35

Max. Case Temp.:

70

Protection Class:

II

IP Rating:

IP20

Operation:

Non-maintained

Function:

AUTO test


Dimension


Installation Diagram

                                     Wire preparation:

                                   0.5~1.5mm⊃2;

AUTO Test

∷ Commissioning test-

Connection of the mains supply will initiate commissioning where the battery will remain on charge for an uninterrupted 24 hours; An interruption of the mains supply will reset the counter to zero.

After 24hours, the luminaire will be put into a duration test for the rated period, immediately followed by another 24hr charge period.

 

∷ Function test-

A 5 second functional test is carried out at 1 week interval.

 

∷ Duration test-

A full rated duration test is carried out at 13 weeks intervals.

System status is indicated by a bi-color LED.

 

LED indication

Status

Commentary

Permanent green

Everything works correctly


One flashed 4 seconds pause

Battery failure

Battery is not connected

Two flashed 4 seconds pause

Battery failure

Battery short or low battery   Voltage

Three flashed 4 seconds pause

Load failure

LED failure

Green and Red off

DC mode

Battery operation (Emergency   mode)


Special Notes

● This product should be installed by a registered electrician in accordance with local standards and electrical regulations;

● Take care to ensure the mains supply is isolated before installation;

● The light source of this luminaire is not replaceable; when the light source reaches its end of life, the whole luminaire shall be replaced;

● The whole luminaire should be replaced when they no longer meet their rated duration of operation after the corresponding recharge period.


Product Inquiry

CB/CE/UKCA Certified IP65 Li-ion Battery Backup Rechargeable LED Emergency Bulkhead Light (LEL04-3L)

CB/CE/UKCA certified IP65 Li-ion Battery Backup Rechargeable LED Emergency Bulkhead Light (LEL03-7L)

CB/CE/UKCA certified LED Battery Backup Rechargeable LiFePO4 Exit Sign Light (LEL02-3LF)

CB, CE, UKCA certified 3W IP20 LED Rechargeable Battery Backup Emergency Recessed Downlight (LEK05-3LF)

3W LED Emergency Light (LEK02-3L)